230 V Lighting Design Guide
Doc. 4859C | crestron.com
17
CLTIBN Terminal Block Installation
CAUTION:
• RISK OF ELECTRIC SHOCK—MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE
THE EQUIPMENT BEFORE SERVICING.
• This equipment is for indoor use only and needs to be air-cooled. Mount in a well-ventilated area. The
ambient temperature must be 0° C to 40° C. The relative humidity must be 0% to 90% (non-condensing).
Terminal blocks are installed along the left side of single-wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are installed along the right side of single-wide enclosures and
side-by-side in the center of double-wide enclosures. When installing modules and terminal blocks in a
double-wide enclosure, be sure to invert units on the right side so that they can be properly wired.
NOTES:
• A licensed electrician, in accordance with all national and local codes, must mount terminal blocks and
modules in a Crestron Automation Enclosure.
• To ensure proper fit, terminal blocks and modules must be installed as indicated in the CAENIB Installation
Guide (Doc. 6562) on the Crestron website.
• Modules and terminal blocks must be installed into the lowest available spaces and continue toward the
top of the enclosure.
• Both left side and right side adhesive wiring labels are provided. The left-side labels are used in both
single and double-wide enclosures. The right-side labels are only used in double-wide enclosures.
• CLTI-4IND and CLTI-2IND terminal blocks should be installed at the top of a CAENIB enclosure and grouped
with other CLTI-4IND and CLTI-2IND terminal blocks.
• Use copper conductors only—rated 75° C.
• LINE and NEUTRAL lines can be jumped to other terminal blocks in the enclosure.