
Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide – DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
49
SETUP: OTHER SETTINGS
SETUP:
OTHER SETTINGS
Wide Range Cool:
Run Fan in Ht Calls:
Auto DdBand Deg:
Disable Auto Mode:
N
N
2
0
N
EXTENDED COOL SETPOINT
RANGE 38-99F (3-37C)
Wide Range Cool: Extends cool setpoint to full auto range of
38º – 99º F (3º – 37º C).
Run Fan in Ht Calls: If the heating system requires fan
control, select Y.
NOTE: Most heating systems run the fan automatically.
Auto Mode Dead Band: Select 2 – 6. The minimum
differential between heating and cooling setpoints (Dual
Setpoint Auto set to Yes in “Display Options”).
Disable Auto Mode: Does not display Auto on “System
Mode” screen and does not permit entering Auto mode even
SETUP: SENSORS
SETUP: SENSORS
SENSOR
INTERNAL:
REMOTE 1:
REMOTE 2:
>TEMP HUM
USE OMIT
SLAB
DETECTED: 1 x T
INTERNAL: Choose USE or OMIT. Choose USE to permit
temperature averaging.
NOTE: Sensor temperature and humidity can be output to
network even if OMIT is chosen.
REMOTE 1 and 2: Choose USE, OMIT, OD (outdoors), or
SLAB (remote sensors only).
NOTE: REMOTE 1 and REMOTE 2 options do not appear
on this screen if these sensors are not connected.
NOTE: Thermostat auto-detects connected remote sensors.
SETUP: HUMIDITY SENSORS
SETUP: H-SENSORS
TRIM
INTERNAL: -5
REMOTE 1: 0
REMOTE 2: 0
% RH
45
50
30
TRIM (-9 – +9) Allows the user to calibrate the INTERNAL,
REMOTE 1 and REMOTE 2 humidity sensors to match %
RH values obtained by other equipment. The values here are
based on a logarithmic index and are not to be interpreted as
units of measurement.
NOTE: For best results, calibration should be performed
when RH is 40% or higher.
Kommentare zu diesen Handbüchern