9” Wall Mount Touch Screen Crestron TPMC-9L
Setup
Network Wiring
When wiring the Cresnet network, consider the following:
• Use Crestron Certified Wire.
• Use Crestron power supplies for Crestron equipment.
• Provide sufficient power to the system.
CAUTION: Insufficient power can lead to unpredictable results or damage
to the equipment. Use the Crestron Power Calculator to help calculate how
much power is needed for the system (
www.crestron.com/calculators).
For Cresnet networks with 20 or more devices, use a Cresnet Hub/Repeater
(CNXHUB) to maintain signal quality.
For more details, refer to “Check Network Wiring” on page 37.
The TPMC-9L can also use high-speed Ethernet for communications between the
device and a control system, computer, media server and other IP-based devices.
For general information on connecting Ethernet devices in a Crestron system, refer to
the Crestron e-Control
Reference Guide (Doc. 6052) at
www.crestron.com/manuals
.
Identity Code
NOTE: The latest software can be downloaded at www.crestron.com/software.
Net ID
The Net ID of the TPMC-9L has been factory set to 03. The Net IDs of multiple
TPMC-9L devices in the same system must be unique. The Net ID is set using the
internal setup menu (refer to “Cresnet” which starts on page 20). Net ID may also be
set from a personal computer (PC) via Crestron Toolbox™ (refer to “
Establishing
Communication” which starts on page 33).
When setting the Net ID, consider the following:
• The Net ID of each unit must match an ID code specified in the Crestron
Studio™ or SIMPL Windows program.
• Each network device must have a unique Net ID.
For more details, refer to the Crestron Toolbox help file.
IP ID
The IP ID is set within the TPMC-9L’s IP table using the internal setup menu (refer
to “IP Table” which starts on page 16
). IP ID may also be set from a PC via Crestron
Toolbox. For information on setting an IP table, refer to the Crestron Toolbox help
file. The IP IDs of multiple TPMC-9L devices in the same system must be unique.
When setting the IP ID, consider the following:
• The IP ID of each unit must match an IP ID specified in the Crestron Studio
or SIMPL Windows program.
• Each device using IP to communicate with a control system must have a
unique IP ID.
12 • 9” Wall Mount Touch Screen: TPMC-9L Operations & Installation Guide – DOC. 7030F