Crestron CHV-TSTATEX infiNET EX™ Thermostat
Setup Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
Aux-Heat Balance
Point
(will only appear for
Heat pump type
systems)
Ab
16 to 90 (for
Fahrenheit) or
-9 to 32 (for Celsius)
or Disabled (--)
--
Aux heat operation is locked out
when outdoor temperature exceeds
the Aux Heat Balance Point. Dual-
fuel systems do not allow both the
heat pump and the aux to run at the
same time.
Interstage Differential
(will only appear for
Heat pump systems)
dF
05 to 80 (tenths of a
degree Fahrenheit),
adjustable in 5 tenths
degree increments or
05 to 45 (tenths of a
degree Celsius),
adjustable in 5 tenths
degree increments
20 (F) or
10 (C)
Heat pump systems can allow both
the heat pump and aux to run at the
same time. This sets the ambient
temperature threshold to trigger aux
heat in addition to the heat pump.
Heat pump/AUX or any
2-stage system
configuration
(will only appear for
Heat pump type
systems)
AS 1 – 6 6
Accumulated staging threshold
index sets how aggressively staging
is performed in response to
extended system calls. Index 6
effectively disables accumulated
staging effects.
Remote sensors Sn i, r, ir i
i – internal sensor only
(When no remote sensor is
detected, only this option is
available)
r – remote sensor only
(Only available when a remote
sensor has been detected)
ir – average internal and remote
sensors
Check Firmware
Version
rE
Firmware version is
displayed in xx.yy.zz
format. “—“ can also
be displayed
--
When firmware version is not yet
shown, display will be “—“. Each
press of the
or button will
cycle to the next portion of the
version number.
InfiNET-EX ID
(RF ID)
id 01 and 03 – FE 01
Sets the infiNET EX ID. SIMPL
Windows restricts infiNET EX
devices to an ID range of 03 – 20.
infiNET EX Sleep Time SL Short (S) or Long (L) L
Indicates thermostat update rate.
Setting for fewer updates (“L”) will
conserve battery power.
Start infiNET EX
Acquire
AC
Not started (--)
In progress
(flashing --)
Finished, found GW
(00)
Finished, could not
find GW (E#, where
# represents an error
code)
N/A
Used to acquire the device to a
gateway.
”E0” indicates that search time has
expired and no gateway was found.
”E1” indicates the infiNET EX RF
Channel is set to “0” (disabled).
(Continued on following page)
Operations & Installation Guide – DOC. 6989A infiNET EX™ Thermostat: CHV-TSTATEX 21