NOTE: The acquire process can take up to 15 seconds. The acquire process cannot
be aborted.
NOTE: “E1” indicates that search time has expired and no gateway was found.
“E1” indicates the RF channel is set to “0” (disabled). To enable the RF channel,
refer to “Start infiNET EX Acquire” in “Setup Mode Parameters/Functions” which
starts on page 20.
Leaving an infiNET EX Network
To leave a network, press and hold the FAN, and buttons simultaneously for
five seconds. Press MODE until the unacquire function is displayed (UA). Press
or
on the CHV-TSTATEX to start the unacquire process. Once completed, press
FAN on the thermostat to exit Setup mode.
Verifying Communication Status
To verify communication status, enter the Setup mode as described in “Basic
Thermostat Setup” on page 17. Press MODE until the “CC” function is displayed.
Press or on the CHV-TSTATEX to verify the communication status.
Communication Error Codes
ERROR
CODE
SUMMARY CORRECTIVE ACTION REMARKS
00 Success None. No detectable problems found.
E0
Low battery
warning
Check and/or replace
batteries, investigate
battery drain rate.
Set when the capacity is below approximately 10%
and the device needs battery power (i.e. not using
24VAC mode).
E1
24VAC supply
usage warning
Confirm desired power
connection and S2
position setting.
Set when constant 24VAC is detected but the
internal bus voltage does not meet run threshold.
This can happen when 24VAC is available but S2
is set to power-steal. This is not an error but warns
that better performance may be achieved by
changing S2 position.
E2
Display timing
error
None, consider
replacement of unit.
Set when timing parameters for display operation
cannot be met. Device may be usable but proper
display operation cannot be guaranteed.
E3
NV memory
usage error
Replace unit when
feasible.
Set when internal NV memory usage has
exceeded its rated life. Device will continue to
operate but data retention may be in question.
E4
Application LQI
poor
Perform general RF
debugging to improve
communications.
Link quality to gateway is poor and may indicate
communications problems that can impact timely
data exchange or battery life.
E5
GW addressing
info missing
Run acquire operations if
communication is needed.
Device cannot address a gateway. This may
simply mean the device has not been acquired
yet.
E6
ZigBee network
join error
Run acquire operations if
communication is needed.
Device is not joined to a ZigBee network. This may
simply mean the device has not been acquired
yet.
E7
Excessive link
cost
Perform general RF
debugging to improve
communications
Network link to gateway is not desirable.
Communication may work ok but is subject to
many hops that will impact communication speed
and battery life.
18 infiNET EX™ Thermostat: CHV-TSTATEX Operations & Installation Guide – DOC. 6989A