Reference Guide Crestron 3-Series Control Systems
28 3-Series Control Systems Reference Guide DOC. 7150A
Control Subnet
The AV3, PRO3, and CP3N (referred to as control systemfor the rest of this
section) have a dedicated Control Subnet which allows for dedicated communication
between the control system and Crestron Ethernet devices without interference from
other network traffic on the LAN.
The
Control Subnet can host up to 64,000 Crestron Ethernet devices. Connect a
Crestron Ethernet switch such as the CEN-SWPOE-16 16-Port Managed PoE Switch
(sold separately) to the control systems CONTROL SUBNET port to use as a
connection point for a variety of Crestron Ethernet devices. The CONTROL
SUBNET port is used to communicate with Crestron Ethernet devices on a subnet
that is independent of the local area network connected to the LAN port. When using
the Control Subnet, observe the following:
The control system acts as a DHCP server to all devices connected to the
Control Subnet and assign IP addresses as needed.
A DNS server is built in to the control system to resolve host names.
Only Crestron Ethernet devices should be connected to the Control Subnet.
The control system can operate in Isolation mode. Take the following into account
when operating in Isolation mode:
Devices on the Control Subnet do not have access to any resources on the
LAN side. This means that if a touch screen with a smart object that
requires Internet access is installed on the Control Subnet operating in
Isolation mode, the smart object cannot work.
Devices on the LAN do not have access to any devices on the Control
Subnet. This includes Crestron Toolbox when it is connected to the LAN.
To configure devices on the Control Subnet with Crestron Toolbox, the PC
running Crestron Toolbox must be physically connected to the Control
Subnet.
Any NAT/Portmapping rules that were previously created do not work
when the control system is in Isolation mode.
CAUTION: Do not connect the CONTROL SUBNET port to the LAN. The
CONTROL SUBNET port must only be connected to Crestron Ethernet devices.
NOTE: If the control system is operating in Isolation mode, Crestron Ethernet
devices that require Internet access should not be connected to the CONTROL
SUBNET port (either directly or indirectly). Any Crestron Ethernet device that
requires an Internet connection should be connected to the local area network.