iLux
™
Lighting Systems
Physical Description
NOTE: The CLSI-C6 units require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.
The following illustration shows the overall dimensions
for the CLSI-C6 and CLSI-C6M.
The following tools/hardware are required for installation.
CLSI-C6M Overall Dimensions
• A 4-gang electrical box (not supplied), 3.5 inches
deep, minimum.
8.89 in
(22.58 cm)
4.48 in
(11.38 cm)
1.88 in
(4.77 cm)
2.38 in
(6.05 cm)
0.59 in
(1.49 cm)
CLSI-C6
0.72 in
(1.83 cm)
CLSI-C6M
• Phillips torque screwdriver (not supplied)
• Four 7/8-inch pan head Phillips screws
(supplied)
If the planned configuration includes connection to shade
controllers, keypads, and/or a Crestron 2-Series control
system, the following items are also required. Refer to the
latest version of the Crestron CLSI-C6 & CLSI-C6M
iLux Lighting System Operations Guide, Doc. 6347, for
detailed configuration options.
• Cresnet network cable(s) (not supplied)
Industry Compliance
• Terminal block connector(s) (two supplied)
These units have been designed to comply with IEC
60669-2-1 and specifications for CE marking. Formal
approval is pending.
Check that any required Cresnet wiring has been installed
and verified. Then, use the following procedure to install
the iLux unit (CLSI-C6M is shown in the illustrations).
Important Notes
1. Feed the wires (power line from the distribution
panel, load wires, plus any required Cresnet
cables) through the holes in the wallbox. Then
install the box in the wall.
Read before installation.
• Codes: Install in accordance with all local and
national electrical codes.
2. Hold the rear of the CLSI-C6M unit and remove
the front panel and cover assembly by carefully
Remove the control panel overlay from the u
• Wiring: Use copper wire only. For supply
connections, use wires rated for at least 75°C.
pulling out and up from the bottom edge.
3. nit
4. of
d
• Lighting Load Types: incandescent, magnetic
low voltage, neon/cold cathode, and non-dim
lighting.
• Temperature: The iLux units are designed for
use where temperatures are between 32° to
104°F (0° to 40°C).
• Wallboxes: The iLux units mount in standard
4-gang wallboxes; 3.5 inches deep, minimum.
• Make certain that power is turned off, and
ensure that there is at least 12 inches of open
space above and below the electrical box
location to permit heat dissipation.
Installation
(it lifts off – is held in place by small tabs) to
reveal the upper mounting screw holes.
Refer to the following diagram for connection
WARNING: Turn off power at the distribution panel
circuit breaker. Installing with power on can result in
serious personal injury and damage to the device.
the AC wiring. All wires to be inserted in the
screw terminals should be stripped 7/16-inch,
and screws should be tightened to between 8 an
10 in.-lbs. (0.90 Newton meters to 1.13 Newton
meters). The maximum wire size is 12 AWG
(3 mm²).
CAUTION: To reduce the risk of overheating and
possible damage to other equipment, do not install to
control a receptacle or a motor-operated appliance.
2 • iLux
™
Lighting Systems: CLSI-C6 & CLSI-C6M Installation Guide – DOC. 6413B