Crestron CAEN Automation Enclosures
Installation
The enclosure must be mounted by a licensed electrician
in accordance with all national and local codes. Refer to
the table on the first page for the weight of a fully loaded
enclosure.
When choosing components to place in the enclosure,
refer to the table on page 1 to ensure that the maximum
weight capacity is not exceeded. Each module’s product
page on the Crestron website lists the module’s weight.
CLT terminal blocks must be mounted using the column
of screw holes shown in the “Mounting Details
diagrams.
CAUTION: These enclosures house equipment that
needs to be air-cooled. Therefore, mount in a
well-ventilated area. The ambient temperature range
should be 32°F to 104°F (0°C to 40°C). The relative
humidity should range from 10% to 90% (non-
condensing). Furthermore, allow adequate clearance in
front of the vented cover for servicing and ventilation.
NOTE: Unless otherwise indicated, the lighting system
specified in this guide is modular, requiring assembly in
the field by a licensed electrician, in accordance with all
national and local codes.
If a UL Listed panel is required, Crestron offers this
service through its UL Listed panel shop. This includes
complete in-factory system configuration and assembly
by Crestron for an additional fee.
NOTE: Install modules into the lowest available spaces
and continue toward the top of the enclosure.
NOTE: Enclosures are intended for indoor use only.
NOTE: When flush mounting, 5/8 in (16 mm) drywall is
preferred.
Wiring
CAUTION: All power feeds must be protected by 15 or
20 amp circuit breakers (supplied by others).
NOTE: Use copper conductors only rated 60°C.
NOTE: All wiring must be installed in accordance with
all local and national electrical codes.
NOTE: Two snap bushings are supplied. If required,
insert into knockouts at the bottom of the enclosure to
prevent damage to low voltage wiring.
Class 1 and Class 2 field wires must be kept separate.
Refer to the following illustrations showing single-wide
and double-wide wiring details. Areas for high voltage
(Class 1) wiring are shown along the top and side(s) of
the unit. The lower area is reserved for low voltage
(Class 2) wiring.
Tighten all CLT-Series terminal block screws and
grounding terminal block screws to the torque specified in
the Torque Datatable.
CAUTION: Failure to properly tighten the screws may
result in poor electrical connection and overheating of the
terminals.
Torque Data
CLT Terminal
Blocks
Grounding Terminal
Blocks
Wire Range
22 - 10 14 - 10 8 6 - 4
Torque (In-Lbs)
9 35 40 45
Key - Typical Products in a CAEN Enclosure
Mounting Details - Single-Wide CAEN
Mount CLT terminal blocks and CLX
modules to the holes shown above.
Mount CLT
to these holes.
Mount CLX
to these holes.
Installation Guide DOC. 5940E Automation Enclosures: CAEN 3